Close

EN54-28 Non-Resettable Linear Heat Cable (Digital)

New EN 54-28 500m cable 78°View larger

EN54-28 500m cable 78°

P-ADE78-0500

EN54-28 is a referenced standard in AS1670.1  2018 and 2024 versions

The ADE range of digital LHD cables contains a pair of twisted, low resistance, tri-metallic conductors sheathed with advanced temperature sensitive polymers. The cable operates by softening the insulation of the conductors, the tension of the twisted conductors then causes the two cores to fuse together. The sensor cable is used in combination with the controller and end-of-line (EOL) unit, and can connected to any fire monitoring equipment through any monitored input i.e. conventional detection zone or addressable interface unit to signal an alarm condition.

EN54-28 is a referenced standard in AS1670.1  2018 and 2024 versions

The ADE range of digital LHD cables contains a pair of twisted, low resistance, tri-metallic conductors sheathed with advanced temperature sensitive polymers. The cable operates by softening the insulation of the conductors, the tension of the twisted conductors then causes the two cores to fuse together. The sensor cable is used in combination with the controller and end-of-line (EOL) unit, and can connected to any fire monitoring equipment through any monitored input i.e. conventional detection zone or addressable interface unit to signal an alarm condition.

Product Information

Alarm location 
The control unit can identify along the length of the sensor cable where an alarm condition has occurred. The alarm location is then indicated on the display of the controller. Both zone are displayed at the same time.

Cable fixings for all applications 
A range of ‘edge’ ,’A’ , ‘P’ , and ‘T’ clips allow the cable to be properly installed. The clips provide heat insulation as well as holding the cable at the correct distance from cable trays, steel works, ceilings and walls.

Key Features

  • Low-Smoke Zero Halogen
  • Up to 1000 m
  • Detection along total cable length
  • Flame retardant
  • Simple low maintenance installation
  • RoHS compliant

Technical Specifications

  • Operating voltage 0 to 49 VAC, 0 to 74 VDC
  • Alarm temperature (typical) +78°C
  • Resistance: 2.5 ohm per m
  • Capacitance: <100 pF per m
  • Inductance: <3.2 uH per m
  • Physical dimensions: Diameter 5.72 mm +/- 0.12 mm (0.225” +/- 0.0005”)
  • Colour: Red
  • No. of cable cores: 2
  • Insulation: 1kV
  • Relative humidity: 0 to 98% noncondensing
  • Ambient temperature: -40 to +45°C